Copyright ©2006 - Inspired Interfaces


PowaMaster Revision Notes

 

 Patches


=================================================================================================
Patch 14 Build 844 - 2006/07/27

Bug Fixes:
1. OLE - Adding multi section lines without having the conductor defined in the library caused an internal error.

=================================================================================================
Patch 13 Build 842 - 2006/03/27

Bug Fixes:
1. Fixed a Transformer issue where by editing Transformer, it would modify the data library's transformer's values as well.

New Functionality:
1. Instead of automatically swapping the transformer's Vmin & Vmax tap settings if the user incorrectly swapped them around, there will now be a user displayed message.

=================================================================================================
Patch 12 Build 840 - 2006/03/16

Bug Fixes:
1. Fixed a Transformer tap issue where if the Transformer's tap settings were corrupted by using the change tool to set the transformer tapping.

New Functionality:
1. By using the Source Defaults in options, the user now has the option to decide how the Source Impedance/Fault levels will be affected by changing the system voltage.

=================================================================================================
Patch 11 Build 838 - 2006/03/13

Bug Fixes:
1. Fixed a colour display issue on Printing where lines would print in a silvery-grey instead of black.

=================================================================================================
Patch 10 Build 836 - 2006/03/10

New Functionality:
1. Dongle License Reset function in the event of corruption of the license.

=================================================================================================
Patch 9 Build 834 - 2006/02/20

Bug Fixes:
1. Fixed an issue where a Transformer would be changed/duplicated in the Data Library when the user changed a transformer from one to another in the project file.
2. Fixed the incorrect harmonic current display on the transformer results.

=================================================================================================
Patch 8 Build 832 - 2006/02/02

Bug Fixes:
1. Fixed the Data Library where a change of a specific item didn't trigger the update button to enable.
2. Fixed a problem on the Load Category where the CF & SF fields were swapped around when opening a project file.
3. Fixed a problem on the calculation of Subtransient Fault Contribution resistance on induction motors.

New Functionality:
1. Introduced Margins on printing.
2. Introduced borders on printing.
3. Curve weight has been increased for protection curves to make it more legible.
4. Curve printing quality has been improved slightly.
5. Graph Title can be changed before printing of a graph.

=================================================================================================
Patch 7 Build 830 - 2005/01/07

Bug Fixes:
1. Fixed a colour display issue on a Text Device.
2. Fixed the Status change of a device to refresh the bus Fault contributing impedance.

=================================================================================================
Patch 6 Build 822 - 2004/10/13

Bug Fixes:
1. Harmonics Triplens modelled incorrectly.

=================================================================================================
Patch 5 Build 820 - 2004/10/6

Bug Fixes:
1. Data values lost on creation of devices.
2. Transformer Details not saved when study saved as an Excel file.
3. Results saving to Excel excluded some items or split results over multiple files.
4. Transformer quantity was not applied to earthing impedances.
5. Transformer harmonic derating factor reported incorrectly on user reports.
6. Ph-G and Ph-Ph-G fault flows reported incorrectly on Transformer Primary or Secondary.
7. Triplen Harmonics modelling through transformers were handled incorrectly.
8. Delete button prompts "delete selection" when first used if nothing is selected.
9. User defined curves imported incorrectly (adding additional values).
10. Protect against empty protection device names read in from previous versions.

New Functionality:
1. Complex numbers are exported into individual columns in the excel export.
2. Consistent units are used in the excel export.
3. Excel export has been sped up.
4. Graph export jpg quality has been improved.
5. User report can be generated for selected items.

=================================================================================================
Patch 4 Build XXX - Not released

1. Fixed a bug where if you delete some protection devices from the Data Library, you will not be able to save the changes.
2. Automatically saves the file to the current version if project is read in from a previous version.
3. Fixed a bug where the protection device is not scrolled into view on the 'Find' functionality.
4. Fixed a bug where placing an empty protection device will cause the file to incorrectly read in protection device settings again.
5. Included a Security fix to disable the display of excel on the ASP server model.

=================================================================================================
Patch 3 Build 796 2003/11/6

1. Fixed the sorting on the user-defined protection curve. It is now based on time from high to low.
2. Fixed a colour display issue on the Protection device.
3. Fixed Display attributes for some devices not displaying the correct attributes on editing.
4. Removed Protection Name sorting in the DataLibrary Editor.
5. Added List position functionality on the Protection Devices.
6. Fixed a bug where the file gets saved to the last accessed folder instead of its own folder.

=================================================================================================
Patch 2 Build 792 2003/10/16

1. Fixed misspelled Microsoft under File save as Filter.
2. Removed the status menu item from the Series Capacitor and Series Reactor (It takes on the Branch Status automatically).
3. Made the Softkey more fault tolerant where it resets itself under certain conditions.

=================================================================================================
Patch 1 Build 790 2003/10/13

1. Fixed lost Transformer User Codes when reading in a project file from a previous version.

=================================================================================================
Released Version Build 788 2003/10/3

 


Home