8 - Build 1288 26 September 2006
1) 3-phase domestic
connection Diversity correction factor for empirical method clipped the
current. e.g. 3kVA ADMD with Imax = 60 A clipped current to 20A (see
domestic graph in Options)
Patch
7 - Build 1286 25 September 2006
1) Deleting
Conductors from data library - Conductor was not deleted from Conductor
groups (fixed in this build)
Patch
6 - Build 1284 21 September 2006
1) User Options
saving/reading improvements - Load category data (ADMD settings per
category improved)
2) Ability to accommodate more conductors in conductor groups (increased
from a total of 500 to 10000)
3) Improvement in Excel OLE links for "Data Library OLE.xls", "Rm_ole.xls",
"GetSet.xls"
Patch
5 - Build 1280 13 September 2006
1) User Options
saving/reading improvements
2) Security DLL update to improve Oracle User Option saving/reading
Patch
4 - Build 1278 31 August 2006
1) OLE Modifications
/ Additions
Parameter Integrity checks for Transformers and Regulators
----------------------------------------------------------
The CreateTrfrNodeEx1 CreateRegulatorNodeEx functions are expanded to
enable parameter integrity checks (e.g checks if the impedance values
are valid). Doubles and Integers can be assigned a special unkown value
of 9999 and bytes that represent boolean values (e.g LockTap Flag) can
be assigned a special unkown value of 2. In these cases, or when obvious
errors are entered such as negative impedance, ReticMaster will search
the data library for an existing transformer and/or regulator and will
use the data parameter of the found transformer and/or regulator. If the
transformer and/or regulator do not exist in the library, then
ReticMaster will use the first transformer and/or regulator n the data
library to assign valid parameter data.
GetSecurityModel function
This function returns an integer depending on which security model is
used
Result = 0 for dongle based security
Result = 1 for software based security
Result = 2 for server based security
DoLogin function
Login function for server based security
DoSilentLogin function
Silent Login function for server based security
DoLogOff function
Login function for server based security
IsLoggedIn function
Test if logged in for server based security
Get_ShowMessages function
Returs existing "show messages" flag in Options
Set_ShowMessages function
Sets/Cancels "show messages" flag in Options
SetDataLibraryReadOnly function
Set Data Library file as Read Only - or remove Read Only flag
2) New Data Libraries are added to the Setup with revised
VoltagewConductor and Trfr Data:
Data Library.mdb - default from build 1278
Data Library.ii
Data Library Template.mdb1
Data Library OLE.xls
3) New ReticMaster help file released
4) Motor Starting simulation - improvent in capturing the start and end
data points
Patch 3 - Build 1266
03 August 2006
1) A new Property (ShowMessages) is available via OLE, for the
suppression of error messages.
2) Text data library file saving (e.g. Data Library.ii) is updated to
handle more conductors in conductor groups
3) ReticMaster file saving (e.g. Data Untitled.rmd) is updated to
handle more conductors in conductor groups
4) User Options (Tools\Options) are saved to Oracle or MSSQL database
if the user is logged on, otherwise in Windows Registry as per existing
functionality.
5) A new security dll (IILibS.dll) is required to accommodate the User
Option saving functionality to Oracle and MSSQL.
6) Options/Domestic - DCF curve formula using British and DT curves for
3-phase ADMD corrected (out by factor 3)
7) New Data Libraries are added to the Setup with revised Conductor and
Trfr Data:
Data Library.mdb
Data Library.ii
Data Library Template.mdb1
Data Library OLE.xls
8) Data Library.mdb and Data Library Template.mdb1 updated voltage
table to accommodate 19.053kV (field size increased)
9) Motor Start profiles improved (not required to add two start and two
end data points any more)
=================================================================================================
Patch 2 - Build 1259
06 June 2006
1) OLE - Changing node status opens\closes node properly
2) OLE - Transformer SetData routines : improvements on phase
connection checking
=================================================================================================
Patch 1 - Build 1257
02 June 2006
1) Data Library path is saved in Options
2) OLE functions will create transformer and regulator data with all
the specifications as set by the calling application e.g. SmallWorld or
Excel. If the data entry does not exist then it will be created.
3) The Change Down tool, Domestic Unbalance routine, had a small bug
where the balancing method transferred service connections from service
cables to the LV backbone (correct), did the balancing (correct), but
the required transfer of balanced service connections from the backbone
to the service cables did not happen (incorrect). This has been fixed.
=================================================================================================